Kyoritsu 6310 Power Meter

Written By Anonymous on September 08, 2012 | 3:05 AM

Distributor Kyoritsu Indonesia ,Multimeters ,Voltage Tester ,Clamp Meters ,Insulation Testers ,Earth Testers ,Loop/PSC/RSD Testers ,Loggers ,Multi Function Testers ,Portable Appliance Testers ,Power Meters

Power Quality Analyzer

KEW 6310
Can measure Flicker in accordance to IEC 61000-4-15 and EN50160 standards. Using our Flicker sensor, available as optional accessory, Pst value (short term severity in 10 minutes value) and the Plt value (long term severity in 2 hours value) can be measured.
12 kinds of Power Measurements for Power Control and Applicable to Power Quality Control including Harmonics Analysis.
One click easy-to-use operation helps complicated setting and processing of large data through the setting / analyzing software provided as accessory.
Direct communication with PC via USB cable

Built-in Input / Output Function of external signal enables the signal transmission to alarms.
2-way power supply by AC and Battery, and Nickel hydrogen battery usable with rechargeable function.
Pull / Insert of CF card possible whenever on recording under the function of memory backup device.
Can monitor insulation at leakage current by using optional leak clamp sensors.
Built-in Print Screen Function enables to record display screen
(Records 512 screens by using CF card: 1 screen 40KB).
Can display Waveform and Vector, and can confirm the wiring connection, too.
Complies fully with International Safety Standards IEC 61010-1 CAT.III 600V.
* Attention for KEW6310 customers:

Flicker measurements are possible with firmware of KEW6310 upgrade (Ver.2.01), PC software PQA Master upgrade (Ver. 2.01) and an optional accessory Flicker sensor KEW8325F.

TRUE RMS
Wiring connections 1P 2W, 1P 3W, 3P 3W, 3P 4W
Measurements and parameters Voltage, Current, Frequency, Active power, Reactive power,
Apparent power, Active energy, Reactive energy, Apparent energy,
Power factor (cos θ), Neutral current, Demand, Harmonics,
Quality (Swell/Dip/Instantaneous Stop, Transients/Over Voltage, Inrush Current, Unbalance Rate, IEC Flicker [Pst(1 min)*, Pst, Plt]), Phase Advance Condenser

(*Pst can be shown in details for 1 minute intervals.)
Other functions Digital output function, External communication function,
Scaling function
Voltage :
Ranges [RMS] 150 / 300 / 600 /1000V (CF: 2.5 or less, 100% or less of each range)
Allowable input 10~110% of each range (1000V range : 20%~)
Display ranges 5~120% of each range
Accuracy |±0.3%rdg±0.2%f.s. (sine wave, 45~65Hz)
Current :
Ranges [RMS]
8128 ( 50A  type ) : 1 / 5 / 10 / 20 / 50A
8127 ( 100A  type ) : 10 / 20 / 50 / 100A
8126 ( 200A  type ) : 20 / 50 / 100 / 200A
8125 ( 500A  type ) : 50 / 100 / 200 / 500A
8124 ( 1000A  type ) : 100 / 200 / 500 / 1000A
8129 ( 3000A  type ) : 300 / 1000 / 3000A
(CF:3.0 or less. 90% or less of each range)
Allowable input 10~110% of each range
Display ranges 1~120% of each range
Accuracy |±0.3%rdg±0.2%f.s. + Accuracy of Clamp sensor
(sine wave, 45~65Hz)
Activa power accuracy |±0.3%rdg±0.2%f.s. + Accuracy of Clamp sensor
(Power factor 1, Sine wave, 45~65Hz)
Influence of power factor |±1.0%rdg (reading at power factor 0.5 against power factor 1)
Frequency meter range 40~70Hz
Internal memory
1.8MB
Measurement file (CSV) : 256kB×6 blocks (=1.536MB)
Screen file (BMP) : 32kB×7 blocks (=0.224MB)
Configuration file (KAS) : 32kB
Display 320×240 (RGB) Pixel, 3.5-inch color STN display
Temperature & humidity range 23ºC±5ºC, Relative humidity 85% or less (no condensation)
Storage Temperature & humidity range -20ºC±60ºC, Relative humidity 85% or less(no condensation)
Operating Temperature & humidity range 0ºC±40ºC, Relative humidity 85% or less(no condensation)
PC Card type *1 Compact flash card
(Capacity: 32 / 64 / 128 / 256 / 512MB / 1 / 2 / 4 / 8GB)

* The CF card larger than 2GB is usable, however, the possible stored size will be limited to 2GB. For example, when the CF card of 4GB or 8GB is used, the maximum stored size will be 2GB.
Applicable standards IEC 61010-1 CAT.III 600V Pollution degree 2
IEC 61010-031, IEC 61326
Power supply AC 100V ~ 240V±10% (45~65Hz)
Alkaline size AA battery LR6 (9V 1.5V × 6) or Ni-MH (HR15-51)
Dimension 175(L)×120(W)×68(D) mm
Weight approx. 900g (including batteries)
Accessories 7141B (Voltage test lead set)
7148 (USB cable)
7170 (Power cord)
9125 (Carrying case)
8307 (Compact flash card 128MB)
8319 (CF Card reader)
Input terminal plate (6-kind)
Alkaline size AA battery (LR6) × 6
PQA MASTER (PC Software)
Quick manual
Cable marker × 32
Optional accessories 8124, 8125, 8126, 8127, 8128 (Load current clamp sensor)
8129 (Flexible clamp sensor)
8146, 8147, 8148 (Leakage & Load current clamp sensor) *2
8141, 8142, 8143 (Leakage clamp sensor) *2
8322 (Compact flash card 256MB)
8323 (Compact flash card 1GB)
8312 (Power supply adaptor)
8325F (Flicker sensor)
9132 (Carrying case (for instrument))
*1: Please refer to here for the CF cards which checked.
*2: Cannot be used for power measurement.

 Set Model

MODEL Clamp Sensor
KEW 6310-01 8125 (500A) × 3
KEW 6310-02 8125 (500A) × 2
KEW 6310-03 8124 (1000A) × 3
KEW 6310-04 8124 (1000A) × 2
KEW 6310-05 8126 (200A) × 3
KEW 6310-06 8126 (200A) × 2
KEW 6310-07 8127 (100A) × 3
KEW 6310-08 8127 (100A) × 2
KEW 6310-09 8128 (5A) × 3
KEW 6310-10 8128 (5A) × 2
KEW 6310-11 8129-03 × 1
KEW 6310-12 8129-02 × 1


 Accessories
6310 × 1
7141B (Voltage test lead set)
7148 (USB cable)
7170 (Power cord)
9125 (Carrying case)
PQA MASTER (PC Software)
Input terminal plate (6-kind)
Quick manual
Alkaline size AA battery (LR6) × 6
8307 (Compact flash card 128MB)
Cable marker × 32
8319 (CF Card reader)
Share this article :

Post a Comment

 
Alamat : Lindeteves Trade Center Lantai UG Jl. Hayam Wuruk,Jakarta. Telp :
Copyright © 2011. Kyoritsu Indonesia by KyoritsuIndonesia - All Rights Reserved.
Mobile/WA : 081297888837
Email : kyoritsu999@gmail.com